75 Watts Power Supply in Metal housing. Free air convection, Galvanic insulated, Continuous short circuit protected, Overload and low voltage protected, Soft start and auto-recovery, High reliability, shock and vibration resistant.
| HSW00751.05T (5V / 7.5A) |
HSW00751.09T (9V / 7.6A) |
| HSW00751.12T (12V / 6.0A) |
HSW00751.15T (15V / 5.0A) |
| HSW00751.24T (24V / 3.2A) |
|
| Model |
HSW00751 |
| Power |
75W |
| Nominal AC Input |
100... 240Vac |
| Input Range AC |
90... 265Vac |
| Input Range DC |
110... 375Vdc |
| Input Frequency |
47... 63Hz |
| Hold-Up Time |
40ms |
| Inrush Current Protection |
NTC <32A |
| Autostart |
Soft start 50ms |
| Output Voltage |
5V |
9V |
12V |
15V |
24V |
| Adjust Range Vout |
4,9... 5,5V |
8,6... 9,9V |
11,4... 13,2V |
14,3... 16,5V |
22,5... 28,5V |
| Ripple & Noise mVpp |
15mV |
15mV |
20mV |
20mV |
50mV |
| Nominal Output Current |
7,5A |
7,6A |
6A |
5A |
3,2A |
| Power Boost <=60°C/60s |
9A |
9,1A |
7,2A |
6A |
3,8A |
| Stability at Load Switch |
±0,1% |
±0,5% |
±0,3% |
±0,2% |
±0,1% |
| Transient Time |
< 1ms |
| Efficiency |
90% |
| Basic load |
Idling-proof |
| Short Circuit Protection |
Continuous |
| Ambient Operation Temperature |
-20°C... +70°C |
| Cooling |
Natural convection |
| Temperature Monitoring |
Upon request |
| Dimensions (WxHxD) |
50x102x96mm |
| IP-Range |
IP20 |
| Safety Norms |
CSA UL CE according to IEC60950-1 |
| Safety IEC |
EN60950-1 EN50178 EN60204-1 |
| Safety Class 1(A) |
VDE0100 VDE0805 |
| Input to Output Isolation |
3000Vac |
| Climatic Class, Humidity |
3k3, 90% non condensing |
| EMI |
EN55022B EN61000-3-2A |
| EMS |
EN61000-6-2,3 |
| MTBF IEC61709 |
500000h |
| Power Good Relay |
Galvanic insulated 60Vdc |
| Sense operation |
Yes 5V-model ±200mV |
| Remote Shutdown |
No |
| Ordering options |
Protective Coating |
| Options |
see Datasheet |
|